Advanced Search
Zhuang Yuxuan, Xuan Jingjing, Li Hao, Zhou Shengqi, Wang Shan, Chen Jing, Dong Shuai, Di Xinyi, Wang Xinyi, Zhang Yuan. Safety Operating Region Assessment Method for Low-Voltage Distributed Photovoltaics Based on Dynamic Operating EnvelopesJ. RURAL ELECTRIFICATION, 2026, (10): 22-28. DOI: 10.13882/j.cnki.ncdqh.2607F063
Citation: Zhuang Yuxuan, Xuan Jingjing, Li Hao, Zhou Shengqi, Wang Shan, Chen Jing, Dong Shuai, Di Xinyi, Wang Xinyi, Zhang Yuan. Safety Operating Region Assessment Method for Low-Voltage Distributed Photovoltaics Based on Dynamic Operating EnvelopesJ. RURAL ELECTRIFICATION, 2026, (10): 22-28. DOI: 10.13882/j.cnki.ncdqh.2607F063

Safety Operating Region Assessment Method for Low-Voltage Distributed Photovoltaics Based on Dynamic Operating Envelopes

  • To address the conservativeness of fixed export limits and the voltage violation risk of conventional dynamic operating envelopes under source-load fluctuations, a safety-margin-based dynamic operating envelope method is proposed for low-voltage distributed photovoltaics. Voltage constraints and photovoltaic export limits are first formulated, and voltage sensitivity is used to determine dynamic operating envelopes under different operating conditions. A safety margin coefficient is then introduced to form a more reliable safety operating region. Case studies on a typical low-voltage distribution network show that the proposed method improves photovoltaic export capability while maintaining nodal voltages within allowable limits, providing a practical reference for safety operating region assessment and export boundary determination.
  • loading

Catalog

    Turn off MathJax
    Article Contents

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return