  • 摘要: 灭弧室是10 kV真空断路器的核心功能单元,其性能状态直接决定断路器的开断可靠性。以某地区配电网在运的1260台ZN63A-12型真空断路器为研究对象,通过对灭弧室触头侵蚀形貌、真空度衰减规律、绝缘劣化特征的系统检测与分析,揭示了灭弧室性能退化的主导机理与演化路径。检测数据表明,运行8 a以上的灭弧室中有23.7%出现触头电磨损量超过设计裕度60%的情况,12.4%存在真空度低于临界阈值的隐患。在此基础上,文章建立了灭弧室退化程度的三级量化评估体系,提出了基于状态评估的差异化检修策略,将检修资源向高风险设备集中配置。工程应用结果显示,优化策略实施后设备故障率下降41.6%,检修成本降低28.3%,验证了该方法的有效性与经济性。

     

    Abstract: The arc extinguishing chamber is the core functional unit of a 10 kV vacuum circuit breaker, and its performance directly determines the reliability of the breaker's interruption capability. This paper takes 1260 ZN63A-12 type vacuum circuit breakers currently in operation within a regional distribution network as the research subject. Through systematic testing and analysis of contact erosion morphology, vacuum degradation patterns, and insulation deterioration characteristics, the dominant mechanisms and evolution pathways of arc extinguishing chamber performance degradation are revealed. Test data indicate that among arc extinguishing chambers operating for over eight years, 23.7% exhibit electrical wear exceeding 60% of the design margin, while 12.4% show potential risks with vacuum levels below critical thresholds. Based on these findings, a three-level quantitative assessment system for arc extinguishing chamber degradation is established, and a differentiated maintenance strategy based on condition assessment is proposed to concentrate maintenance resources on high-risk equipment. Engineering application results demonstrate that after implementing the optimized strategy, equipment failure rates decreased by 41.6% and maintenance costs were reduced by 28.3%, verifying the effectiveness and economic benefits of this approach.

     

/

返回文章
返回