Abstract:
The arc extinguishing chamber is the core functional unit of a 10 kV vacuum circuit breaker, and its performance directly determines the reliability of the breaker's interruption capability. This paper takes
1260 ZN63A-12 type vacuum circuit breakers currently in operation within a regional distribution network as the research subject. Through systematic testing and analysis of contact erosion morphology, vacuum degradation patterns, and insulation deterioration characteristics, the dominant mechanisms and evolution pathways of arc extinguishing chamber performance degradation are revealed. Test data indicate that among arc extinguishing chambers operating for over eight years, 23.7% exhibit electrical wear exceeding 60% of the design margin, while 12.4% show potential risks with vacuum levels below critical thresholds. Based on these findings, a three-level quantitative assessment system for arc extinguishing chamber degradation is established, and a differentiated maintenance strategy based on condition assessment is proposed to concentrate maintenance resources on high-risk equipment. Engineering application results demonstrate that after implementing the optimized strategy, equipment failure rates decreased by 41.6% and maintenance costs were reduced by 28.3%, verifying the effectiveness and economic benefits of this approach.