Abstract:
To address the significant fire risk caused by failures of temperature control circuits in dry-type box transformers at electrochemical energy storage power stations, this paper systematically analyzes the insulation thermal aging mechanism and fire evolution process of dry-type transformers. The analysis shows that conventional temperature control circuits contain gaps in protection under fault conditions such as temperature controller failure, loss of control power, sensor disconnection, and fan circuit breaker tripping. Accordingly, this paper proposes an optimized temperature control circuit with self-diagnosis, multilevel protection, and power supply decoupling capabilities. The scheme uses several key technologies, including self-diagnostics of the intelligent temperature controller and a normally closed contact output, independent power supplies for the fan and the temperature controller, auxiliary-contact monitoring of the fan circuit breaker, and station-level energy management system (EMS) alarms for temperature limit violations and abrupt temperature changes. An electrothermal co-simulation model compares the thermal responses and protection performance of the conventional and optimized schemes under four typical fault conditions. The proposed scheme uses mature components, requires only minor retrofitting, and offers flexible protection logic. It provides a technical reference for energy storage power stations and other dry-type transformer applications requiring forced-air cooling.