Abstract:
This paper examines a single-phase open circuit on the 10 kV Gx Line at the 110 kV Gz Substation. The resulting ferroresonant overvoltage damages customer equipment and seriously affects the safe operation of the power system. To deepen power utility personnel's understanding of line-break-induced ferroresonance and develop effective suppression measures, this paper analyzes the fault phenomena and accident progression. It constructs an ATP-EMTP-based simulation model of line-break-induced ferroresonance to validate the mechanism analysis and tests the proposed suppression measures through simulation. Based on actual operating conditions at Jimo District Power Supply Company, the paper summarizes the characteristics of line-break-induced ferroresonance in ungrounded systems and the corresponding response methods. It also proposes a feasible and effective set of preventive and mitigation measures. This study advances the understanding of line-break-induced ferroresonance and offers solutions tailored to the Jimo power grid, thereby supporting its safe and stable operation.