Abstract:
The data acquisition completeness rate of 96-point curves serves as a key reference indicator for refined management in modern power systems. It directly affects the calculation results of electricity consumption forecasting, line loss statistics, and other related tasks. This paper systematically analyzes various internal causes of abnormal completeness rates of curve data acquisition during the daily operation of metering equipment and identifies the causes of common problems, including device interfacing errors, dual-line wiring of electricity meters, redundant records in the backend system, and inconsistent parameter settings. Based on the fault mechanisms, a comprehensive rectification and troubleshooting scheme is developed, covering problem investigation, fault type identification, on-site handling, and verification of rectification effectiveness. Meanwhile, a five-step troubleshooting method for accurate fault identification and corresponding requirements for routine maintenance and management are proposed. A unified standard workflow is adopted to systematize and standardize the practical experience accumulated by frontline personnel, thereby establishing a set of operational methods that can be widely applied and used for mutual reference. Without large-scale replacement of equipment in distribution station areas, the overall completeness rate of curve data acquisition is significantly improved.