高级检索

一起35 kV备自投冷倒负荷误报跳闸案例分析

Case Analysis of a False Trip Alarm During a 35 kV BZT Cold Load Transfer Operation

  • 摘要: 集控系统D6000在处理跨站关联操作时,常因单站逻辑局限导致误报。文章以一起35 kV备自投冷倒负荷引发的误报事件为例,分析了“事件化”告警逻辑在非故障性自动切换场景下的缺陷。研究发现,由于缺乏对源端操作行为的辨识,备自投动作产生的“开关变位 + 事故总 + 保护出口”信号组合满足了传统事故判据,导致系统误判。针对此问题,提出引入源端操作性质作为闭锁条件,通过构建跨站拓扑关联约束,解决此类误报问题,为集控系统的广域逻辑优化提供参考。

     

    Abstract: The D6000 centralized control system frequently generates false alarms during cross-station correlated operations, stemming from the inherent limitations of its single-station logic. Taking a false alarm event caused by a 35 kV Backup Automatic Transfer (BZT) cold load transfer operation as an example, this paper analyzes the defects of event-based alarm logic in non-fault automatic switching scenarios. The study finds that, due to the lack of identification of source side operation behavior, the signal combination generated by the BZT action, namely "switch position change, general accident signal, and protection trip", satisfies the conventional accident criteria, leading to system misjudgment. To address this problem, this paper proposes introducing the nature of source side operations as a blocking condition and constructing cross station topological correlation constraints to resolve such false alarms, thereby providing a reference for wide area logic optimization in centralized control systems.

     

/

返回文章
返回