一起数字变电站变压器工频变化量差动误动原因分析

Analysis of Mis-operation of Power Frequency Variation Differential Protection for Transformers in Digital Substations

  • 摘要: 数字化变电站的特点是过程层模拟量采集通过SV网络实现,开关量传输采用GOOSE网络完成,同时配备电子式互感器以实现模拟量的就地数字化,再通过采集单元、合并单元等光纤回路传输至保护测控等装置。文章以一起数字化变电站主变工频变化量差动保护误动事故为例进行技术原因分析,详细剖析了事故过程及处理方法,通过理论分析与仿真实验复现了事故波形,最终确定跳闸事故的原因为互感器至采集单元的屏蔽电缆接头虚焊,导致高压侧传输数据丢失、波形异常,引起主变工频变化量差动保护误动。针对该事故提出了应对措施,以期为解决此类问题提供参考。

     

    Abstract: Digital substations are characterized by the collection of analog signals at the process layer via the Sampled Value (SV) network and the transmission of switching signals through the GOOSE network. Electronic transformers are employed to achieve on-site digitization of analog signals, which are then transmitted to protection, measurement, and control devices through fiber optic circuits such as acquisition units and merging units. This paper analyzes a typical case of mis-operation of power frequency variation differential protection for a main transformer in a digital substation. A detailed technical investigation of the accident process and handling methods is conducted. Through theoretical analysis and simulation experiments, the accident waveform is reproduced, and it is determined that the root cause of the tripping accident is a cold solder joint at the shielded cable connection between the transformer and the acquisition unit. This defect leads to abnormal waveforms and data loss on the high-voltage side, resulting in the mis-operation of the main transformer's power frequency variation differential protection. Corresponding countermeasures are proposed to address this accident, aiming to provide a reference analysis method for resolving similar issues.

     

/