高级检索

一起10 kV真空断路器分闸不到位故障分析及处理

Fault Analysis and Handling of Incomplete Tripping in a 10 kV Vacuum Circuit Breaker

  • 摘要: 10 kV真空断路器作为变电站内的关键设备,其可靠性对电网的安全稳定运行至关重要。为保证电网安全可靠运行,现场运行要求断路器必须可靠分闸;若无法可靠分闸或分闸不到位,都可能埋下严重的事故隐患。文章针对一起10 kV真空断路器因分闸缓冲器漏油导致分闸不到位的故障,通过现场检查断路器主轴初始位置,进行分合闸时间及同期性、合闸弹跳、分闸反弹、分合闸电磁铁最低动作电压等测试,分析了导致断路器分闸不到位的根本原因,并提出了更换分闸缓冲器的处理方案。

     

    Abstract: As a critical equipment in the substation, the reliability of the 10 kV vacuum circuit breaker is crucial to the safe and stable operation of the power grid. In order to ensure the safe and reliable operation of the power grid, on-site operation requires that the circuit breaker must trip dependably. The inability to trip reliably or incomplete tripping may lead to serious hazards. Focusing on a fault where oil leakage in the tripping damper led to incomplete tripping of a 10 kV vacuum circuit breaker, this paper conducts on-site inspections of the initial position of the circuit breaker's main shaft. Testing is performed on the opening and closing times and synchronization, closing bounce, opening rebound, and the minimum operating voltage of the opening and closing electromagnets. The root causes of the circuit breaker's incomplete tripping are analyzed, and a resolution plan involving the replacement of the tripping damper is proposed.

     

/

返回文章
返回