低压配电网接地系统紊乱引发的外墙带电故障分析

Analysis of Energized Exterior Wall Faults Caused by Grounding System Disturbances in Low-voltage Distribution Networks

  • 摘要: 文章针对民用建筑物外墙和电气设备外壳带电现象,勘察现场、检查低压线路接线接地情况,结合现场测量数据,分析判断故障原因,确定故障原因是低压系统接地形式设置不正确、客户擅改电器接线导致故障扩大。运用仿真软件Matlab验证结果正确性,故障分析与排查过程对解决低压配电网设备外壳带电、线路低电压等常见问题具有参考价值。

     

    Abstract: ThisThis study investigates the phenomenon of energized exterior walls and electrical equipment enclosures in residential buildings. Through on-site inspections and assessments of grounding configurations in low-voltage circuits, combined with field measurement data, the root cause of the fault is identified as improper grounding scheme implementation in the low-voltage system and unauthorized modifications of electrical wiring by customers, which led to an expanded fault voltage. The fault diagnosis is further validated using Matlab. The fault analysis and troubleshoot method presented provide valuable insights for addressing common issues such as energized equipment enclosures and low-voltage in low-voltage distribution networks.

     

/