Citation: | ZHANG Gang, CAI Xiao, LI Ming. Analysis of a Case of 35 kV Bus Differential Protection Action Caused by a Deadband Fault[J]. RURAL ELECTRIFICATION, 2024, (1): 89-90. DOI: 10.13882/j.cnki.ncdqh.2024.01.024 |
This article introduces a 35 kV bus differential protection action event that occurred during the AVC reactor removal process. Causing all switches on the 35 kVⅡ section bus to trip. Based on on-site collection, the cause of switch tripping was analyzed, and the pre control measures were stated.
[1] |
张威, 张知宇, 操晨润, 等. 某220 kV变电站的110 kV正母线母差动作原因分析[J]. 农村电气化,2023(7):19−21.
|
[2] |
陶昆,胡毅. 变电站电流互感器一次引线异常接线方式研究[J]. 农村电气化,2021(11):25−28.
|
[3] |
王风光,李力,吕航,等. 基于电流分布系数的母差保护非故障相饱和判别[J]. 电力工程技术,2020,39(5):197−203.
|
[4] |
张贝贝. 考虑死区故障的馈线自动化技术研究[J]. 农村电气化,2023(7):38−41.
|
[5] |
王风光,李力,吕航,等. 母线保护对死区故障的优化解决方案[J]. 电力自动化设备,2021,41(12):219−224.
|