Analysis of Overheating Defect Caused by Loose Connection of Transformer Bushing Bolt

More Information
  • Received Date: April 27, 2022
  • Revised Date: July 14, 2022
  • This paper introduces the overheating defect of a 35 kV transformer caused by the loosening of the soft connecting bolt at the bottom of the bushing at the low-voltage side. Through the analysis of the three ratio method of chromatogram of the fault transformer oil, it is preliminarily determined that the fault is of high temperature and overheating type. The winding overheating defect is further judged by the auxiliary analysis of"four ratio method". Then conduct power failure high-voltage test on windings at high and low voltage sides of the transformer. Finally, it was found that the DC/T ratio at the low voltage side exceeded the standard. Through disassembly inspection, it was found that the soft connecting bolts at the bottom of the low voltage bushing were loose. The preventive measures are put forward.

  • [1]
    DL/T 722-2014. 变压器油中溶解气体分析和判断导则[S]. 北京: 中国电力出版社, 2014.
    [2]
    黄旭, 王骏. 变压器油中溶解气体分析和故障判断[J]. 石油化工设计, 2021, 38(2): 39-41+6.
    [3]
    GB/T 7252-2001. 变压器油中溶解气体分析和判断导则[S]. 北京: 中国电力出版社, 2002.
    [4]
    徐康健, 汪卫国. GB/T7252-2001《变压器油中溶解气体分析和判断导则》中一问题的探讨[J]. 电力技术, 2009(2): 62-63.
    [5]
    邹剑, 陆瑾, 周晓凡. 四比值法在变压器过热性故障判断中的应用[J]. 变压器, 2011, 48(10): 66-67.
    [6]
    Q/GDW1168-2013. 输变电设备状态检修试验规程[S]. 北京: 中国电力出版社, 2014.
    [7]
    石俏, 刘有为, 方燕虹, 等. 《输变电设备状态检修试验规程》新版技术解析[J]. 现代电力, 2022(5): 623-630.
    [8]
    刘钊, 纪鹏, 白杨. 四比值法在变压器铁芯多点接地缺陷分析中的应用[J]. 农村电气化, 2021(8): 31-33+64.
  • Related Articles

    [1]JIA Yuanzheng, TIAN Jing, YU Jintao, LUO Chaolong, WANG Sijin. Research and Application of Insulating Glove Operation Method for Replacing Pole-mounted Transformers[J]. RURAL ELECTRIFICATION, 2024, (9): 50-53. DOI: 10.13882/j.cnki.ncdqh.2308A035
    [2]ZHANG Hui, JIANG Feng, LIU Zhengmao, ZHOU Jiaxun. Research on the Design of Steel Pipe Poles with Vertical Arrangement Transformed into Horizontal Arrangement for 110 kV Four Circuit Route[J]. RURAL ELECTRIFICATION, 2024, (2): 20-25. DOI: 10.13882/j.cnki.ncdqh.2024.02.005
    [3]WANG Yingfei. Research on the Application of Variable Endpoint Optimal Trajectory Method to Track Maximum Power Point of Three-phase Photovoltaic Grid Connected System[J]. RURAL ELECTRIFICATION, 2023, (5): 62-67. DOI: 10.13882/j.cnki.ncdqh.2023.05.016
    [4]Liu Zhao, Ji Peng, Bai Yang. Applications of Four Ratio Method in Transformer Iron Core Multi-point Earthing Defect Analysis[J]. RURAL ELECTRIFICATION, 2021, (8): 31-33, 64. DOI: 10.13882/j.cnki.ncdqh.2021.08.009
    [5]Xiong Xin, Xi Zhenqian, Yang yi. Three Steps Type Located Method Suited to Steal Electrical Energy Customers Based on Synchronism Line Loss System k Value[J]. RURAL ELECTRIFICATION, 2021, (3): 72-73. DOI: 10.13882/j.cnki.ncdqh.2021.03.023
    [6]Zhou Lawu, Luo Hongbo, Ou Yangming, Wang Xuhong. Normalization Method to Discriminate Connection Groups in Three-phase Power Transformers[J]. RURAL ELECTRIFICATION, 2021, (2): 13-15. DOI: 10.13882/j.cnki.ncdqh.2021.02.004
    [7]Su Xiaolong, Fu Tie. Simple and Easy Analysis Method and Application Concerned in Direct-current Resistance Data for Transformers[J]. RURAL ELECTRIFICATION, 2020, (7): 31-34. DOI: 10.13882/j.cnki.ncdqh.2020.07.009
    [8]Lu Wei, Cheng Long, Yu Weigang. Replace Fuse with Load Based on by-pass Job Method[J]. RURAL ELECTRIFICATION, 2020, (5): 29-30, 39. DOI: 10.13882/j.cnki.ncdqh.2020.05.010
    [9]Luo Liqiong. Applied Research of Four Network Fused Technology Used for Electric Power Communication[J]. RURAL ELECTRIFICATION, 2019, (12): 7-10. DOI: 10.13882/j.cnki.ncdqh.2019.12.002
    [10]Guo Yong, Cheng Chunmeng. Research of County Power Grid Evaluation System Based on Order Relation Method and Entropy Method[J]. RURAL ELECTRIFICATION, 2019, (6): 21-25. DOI: 10.13882/j.cnki.ncdqh.2019.06.005

Catalog

    Article views (0) PDF downloads (1) Cited by()

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return